Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 22, 2022, 11:47 AM
  • 08 0137_08 0136_6222022_050543.mp4

Date
06/22/2022
W/O
0957191
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00006
PipeID
P00193
Time
4:47 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3131
Sewer Name
08 FIGUEROA STREET TRUNK
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
20220622MDM_FIGUEROA_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
08 0137
Downstream MH
08 0136
Dir. of Survey
Downstream
Length Surveyed
340.8 ft.
Total Length
340.8 ft.
Structural Index
2
Structural Quick
3125
Structural Rating
13
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
15
Pipe schematic from manhole 08 0137 to 08 0136
MH: 08 0137MH: 08 0136downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 5:00AM2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start - GREASE COAT ON PIPE15.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped21.6 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - HAIRLINE29.8 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H53.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H63.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped114 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped164.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped275.5 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SLIGHGT279.3 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL327.6 ft. FC - Fracture Circumferential, from 04 to 05 o'clock, within 8 inches of joint: YES - SL340.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish - GREASE COAT ON PIPE340.2 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped340.8 ft. AMH - Downstream Manhole, Survey Ends - 5:35AM

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start - GREASE COAT ON PIPE

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start - GREASE COAT ON PIPE

Observations (17)

DistanceCodeObservation
279.3FCSL
114TFCCapped
0MWL
340.8AMH5:35AM
0MWM
340.2DAGSGREASE COAT ON PIPE
164.5TFCCapped
53.9FLH
340.2MGOConn. @ Mh, 3 O' Clock. Capped
29.8FCH
275.5FCSLIGHGT
2DAGSGREASE COAT ON PIPE
15.9TFCCapped
327.6FCSL
63.2TFCCapped
0AMH5:00AM
21.6FCHAIRLINE

Properties (6)

custom_field_three
SLIGHT & HAIRLINE FRACTURES
custom_field_two
3
customer
LACSD
datetime
2022-06-22T04:47:22-07:00
documentation
MARTIN,REVELES,OLIVER 111,IGNACIO
is_lateral_inspection
false