Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 21, 2022, 03:27 PM
  • 01 1068_01 1067_6212022_084635.mp4

  • 01 1068_01 1067_6212022_091143.mp4

Date
06/21/2022
W/O
0957224
Weather
Dry
Operator/Surveyor
BRAR
Sewer ID
Z00211
PipeID
P01916
Time
8:27 AM
Certificate
SEE REMARKS
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3128
Sewer Name
01 HUNTINGTON PARK RELIEF EXTENSION TRUNK
City
HUNTINGTON PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Maintenance Related
Project
20220621SB_HTON_PK_RE_EX_TR
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
01 1068
Downstream MH
01 1067
Dir. of Survey
Downstream
Length Surveyed
494.6 ft.
Total Length
494.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3225
O&M Rating
16
Overall Index
2
Overall Quick
Overall Rating
16
Pipe schematic from manhole 01 1068 to 01 1067
MH: 01 1068MH: 01 1067downstream0 ft. MGO - General Observation - TWO ACTIVE CONN AT 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 01.1068 8:42 AM0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area75.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"134.6 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"197.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 4"241 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4" - 80% GRESE IN CONNECTION287.9 ft. TFD - Tap Factory Made Defective, at 12 o'clock, -, within 8 inches of joint: YES, 4" - POSSIBLE PIPE IN A PIPE326.7 ft. RTC - Roots Tap Connection, from 11 to 01 o'clock, 30 %, within 8 inches of joint: YES - ROOTS IN SEWER TRUNK326.7 ft. TFD - Tap Factory Made Defective, at 12 o'clock, -, within 8 inches of joint: YES, 4" - 70% ROOTS IN CONNECTION366.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 4"409.1 ft. RMC - Roots Medium Connection, from 11 to 01 o'clock, 15 %, within 8 inches of joint: YES - 15% ROOTS IN SEWER TRUNK409.8 ft. TFD - Tap Factory Made Defective, at 12 o'clock, -, within 8 inches of joint: YES, 4" - 95% ROOTS IN CONNECTION448.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 4" - 10% ROOTS IN CONNECTION486.9 ft. RMC - Roots Medium Connection, from 11 to 01 o'clock, 10 %, within 8 inches of joint: YES - 10% ROOTS IN SEWER CONNECTION486.9 ft. TFD - Tap Factory Made Defective, at 12 o'clock, -, within 8 inches of joint: YES, 4" - 95% ROOTS IN CONNECTION494.6 ft. AMH - Downstream Manhole, Survey Ends - 01.1067 AT 955AM

Observations (18)

DistanceCodeObservation
0MGOTWO ACTIVE CONN AT 9 O'CLOCK
197.8TF
409.8TFD95% ROOTS IN CONNECTION
134.6TFA
0AMH01.1068 8:42 AM
409.1RMC15% ROOTS IN SEWER TRUNK
241TFA80% GRESE IN CONNECTION
448.5TF10% ROOTS IN CONNECTION
366.6TF
494.6AMH01.1067 AT 955AM
0MWL
326.7RTCROOTS IN SEWER TRUNK
486.9RMC10% ROOTS IN SEWER CONNECTION
326.7TFD70% ROOTS IN CONNECTION
0MWM
75.7TFC
287.9TFDPOSSIBLE PIPE IN A PIPE
486.9TFD95% ROOTS IN CONNECTION

Properties (7)

additional_info
U-0618-0703002249
custom_field_three
ROOTS
custom_field_two
4
customer
LACSD
datetime
2022-06-21T08:27:55-07:00
documentation
BRAR, RUVALCABA, SHADLER
is_lateral_inspection
false