Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 18, 2022, 10:04 AM
  • 08 0521_08 0520A_05182022_044643.mp4

Date
05/18/2022
W/O
952096
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00021
PipeID
P25927
Time
3:04 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10116
Sewer Name
08 VICTORIA STREET TRUNK
City
COMPTON
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_952096_TV08031_MAY2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
08 0520A
Downstream MH
08 0521
Dir. of Survey
Upstream
Length Surveyed
265.1 ft.
Total Length
265.1 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
156
O&M Index
2
O&M Quick
2I00
O&M Rating
104
Overall Index
3
Overall Quick
Overall Rating
260
Pipe schematic from manhole 08 0520A to 08 0521
MH: 08 0520AMH: 08 0521upstream0 ft. AMH - Upstream Manhole, Survey Ends - 08 05210 ft. MGO - General Observation - CAPPED CONNECTION @ U/S MH - 1 O'CLOCK.0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK1.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish243.1 ft. RPP - Repair Patch, from 01 to 03 o'clock, within 8 inches of joint: YES - PATCH APPARENTLY MADE OF CONCRETE - SOME OF THE DAMAGE IS WITHIN 8" OF JOINT.253.3 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"261 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start263.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start265.1 ft. MWL - Water Level, 10 %of cross sectional area265.1 ft. AMH - Downstream Manhole, Survey Begins - 05 0520A265.1 ft. MWM - Water Mark, 25 %of cross sectional area

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Repair Patch, from 01 to 03 o'clock, within 8 inches of joint: YES - PATCH APPARENTLY MADE OF CONCRETE - SOME OF THE DAMAGE IS WITHIN 8"  OF JOINT.

    22 ft. - Repair Patch, from 01 to 03 o'clock, within 8 inches of joint: YES - PATCH APPARENTLY MADE OF CONCRETE - SOME OF THE DAMAGE IS WITHIN 8" OF JOINT.

Observations (12)

DistanceCodeObservation
0MWL
265.1AMH08 0521
11.8TBA
265.1MGOCAPPED CONNECTION @ U/S MH - 1 O'CLOCK.
263.7CM
22RPPPATCH APPARENTLY MADE OF CONCRETE - SOME OF THE DAMAGE IS WITHIN 8" OF JOINT.
0AMH05 0520A
4.1CM
265.1MGOCONNECTION AT MH 9 O'CLOCK
0MWM
2DAGS
263.7DAGS

Properties (8)

additional_info
630063051722204
custom_field_three
CRACKS
custom_field_two
2
customer
1
datetime
2022-05-18T03:04:22-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
39052