Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 26, 2022, 10:03 AM
  • 22 0615A_22 0615_04262022_041303.mp4

Date
04/26/2022
W/O
951828
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00827
PipeID
P16963
Time
3:03 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10080
Sewer Name
22 SUNFLOWER TRUNK
City
GLENDORA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_951828_TV22166_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0615A
Downstream MH
22 0615
Dir. of Survey
Downstream
Length Surveyed
161.8 ft.
Total Length
161.8 ft.
Structural Index
3
Structural Quick
3E2E
Structural Rating
153
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
153
Pipe schematic from manhole 22 0615A to 22 0615
MH: 22 0615AMH: 22 0615downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 0615A0 ft. MWL - Water Level, 10 %of cross sectional area2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.1 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO, Start46.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"66 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"91 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"123.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"136.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"157.4 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO, Finish157.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish161.8 ft. AMH - Downstream Manhole, Survey Ends - 22 0615

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
0MGOCONNECTION AT THE MH 3 OC'LOCK
157.4SSS
0MWM
2.1SAV
66TF
5.1SSS
46.1TF
161.8AMH22 0615
123.3TF
0AMH22 0615A
136.1TFC
0MWL
91TF
157.4SAV

Properties (7)

additional_info
630074042522201
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-04-26T03:03:41-07:00
documentation
PROPIPE
is_lateral_inspection
false