Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 26, 2022, 06:07 AM
  • 22 0629_22 0628_04262022_002239.mp4

Date
04/25/2022
W/O
951828
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00827
PipeID
P16977
Time
11:07 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10080
Sewer Name
22 SUNFLOWER TRUNK
City
GLENDORA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_951828_TV22166_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0629
Downstream MH
22 0628
Dir. of Survey
Downstream
Length Surveyed
363.6 ft.
Total Length
363.6 ft.
Structural Index
3
Structural Quick
3M2M
Structural Rating
360
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
360
Pipe schematic from manhole 22 0629 to 22 0628
MH: 22 0629MH: 22 0628downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 06290 ft. MWM - Water Mark, 20 %of cross sectional area2.9 ft. MGO - General Observation - MAG COAT3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.1 ft. SSS - Surface Spalling, from 12 to 02 o'clock, within 8 inches of joint: NO10.1 ft. SSS - Surface Spalling, from 01 to 03 o'clock, within 8 inches of joint: NO12.1 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO, Start22.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"62.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"95.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"115.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"147.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"168.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"196.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"212.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"232.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"249.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"269.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"285.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"322.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"351.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"361.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish361.3 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO, Finish363.6 ft. AMH - Downstream Manhole, Survey Ends - 22 0628

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (25)

DistanceCodeObservation
285.9TFC
361.3SAV
212.6TFC
3SAV
12.1SSS
0MWL
10.1SSS
95.6TFC
232.7TFC
351.1TF
363.6AMH22 0628
0AMH22 0629
322.4TF
147.8TF
249.4TF
269.9TF
62.7TFC
2.9MGOMAG COAT
22.2TF
0MWM
168.5TF
361.3SSS
196.5TFC
115.3TF
3.1SSS

Properties (7)

additional_info
630074042522201
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-04-25T23:07:19-07:00
documentation
PROPIPE
is_lateral_inspection
false