Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 26, 2022, 06:31 AM
  • 22 0628_22 0627_04262022_004655.mp4

Date
04/25/2022
W/O
951828
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00827
PipeID
P16976
Time
11:31 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10080
Sewer Name
22 SUNFLOWER TRUNK
City
GLENDORA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_951828_TV22166_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0628
Downstream MH
22 0627
Dir. of Survey
Downstream
Length Surveyed
365.4 ft.
Total Length
365.4 ft.
Structural Index
3
Structural Quick
3M2B
Structural Rating
244
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
244
Pipe schematic from manhole 22 0628 to 22 0627
MH: 22 0628MH: 22 0627downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 06280 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2.7 ft. MGO - General Observation - MAG COAT2.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"35.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"47.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"59.1 ft. SSS - Surface Spalling, from 08 to 10 o'clock, within 8 inches of joint: NO72.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"96.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"115 ft. SSS - Surface Spalling, at 02 o'clock, within 8 inches of joint: NO124.1 ft. SSS - Surface Spalling, at 02 o'clock, within 8 inches of joint: NO140.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"156.1 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO165.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"170 ft. SSS - Surface Spalling, from 01 to 02 o'clock, within 8 inches of joint: NO191.1 ft. SSS - Surface Spalling, from 10 to 11 o'clock, within 8 inches of joint: NO191.1 ft. SSS - Surface Spalling, from 10 to 11 o'clock, within 8 inches of joint: NO202.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"205.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO205.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO218.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"220 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO246.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"267.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"281.8 ft. TS - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6"287.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"300.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO312.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"317 ft. SSS - Surface Spalling, from 01 to 02 o'clock, within 8 inches of joint: NO317 ft. SSS - Surface Spalling, from 01 to 02 o'clock, within 8 inches of joint: NO320 ft. SSS - Surface Spalling, from 01 to 03 o'clock, within 8 inches of joint: NO336.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"352.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"362.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish365.4 ft. AMH - Downstream Manhole, Survey Ends - 22 0627

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6"

    281.8 ft. - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6"

Observations (37)

DistanceCodeObservation
191.1SSS
287.7TFC
0AMH22 0628
59.1SSS
281.8TS
170SSS
205.1SSS
0MWL
156.1SSS
115SSS
72.1TFC
2.7MGOMAG COAT
220SSS
218.4TF
124.1SSS
317SSS
362.6SAV
336.4TF
317SSS
352.8TF
365.4AMH22 0627
2.7SAV
191.1SSS
320SSS
165.7TF
246.8TFC
96.5TF
267.2TF
11.2TF
300.1SSS
140.9TF
312.1TFC
202.4TF
47.7TF
0MWM
205.1SSS
35.9TFC

Properties (7)

additional_info
630074042522201
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-04-25T23:31:32-07:00
documentation
PROPIPE
is_lateral_inspection
false