Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 26, 2022, 07:18 AM
  • 22 0625_22 0624_04262022_013451.mp4

Date
04/26/2022
W/O
951828
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00827
PipeID
P16973
Time
12:18 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10080
Sewer Name
22 SUNFLOWER TRUNK
City
GLENDORA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_951828_TV22166_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0625
Downstream MH
22 0624
Dir. of Survey
Downstream
Length Surveyed
222.8 ft.
Total Length
222.8 ft.
Structural Index
3
Structural Quick
3H2H
Structural Rating
220
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
220
Pipe schematic from manhole 22 0625 to 22 0624
MH: 22 0625MH: 22 0624downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 06250 ft. MWL - Water Level, 15 %of cross sectional area0.1 ft. MWM - Water Mark, 20 %of cross sectional area2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start17.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"24.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"99.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"185.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"195.2 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"222.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish222.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish222.8 ft. AMH - Downstream Manhole, Survey Ends - 22 0624222.8 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    195.2 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (14)

DistanceCodeObservation
2.1SAV
0.1MWM
17.7TFC
222.2SSS
0AMH22 0625
222.2SAV
185.6TFC
222.8AMH22 0624
24.3TF
222.8MGOCONNECTION AT THE MH 3 OC'LOCK
99.9TF
195.2TB
2.1SSS
0MWL

Properties (7)

additional_info
630074042522201
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-04-26T00:18:42-07:00
documentation
PROPIPE
is_lateral_inspection
false