Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 26, 2022, 09:28 AM
  • 22 0620_22 0619_04262022_034624.mp4

Date
04/26/2022
W/O
951828
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00827
PipeID
P16968
Time
2:28 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10080
Sewer Name
22 SUNFLOWER TRUNK
City
GLENDORA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_951828_TV22166_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0619
Downstream MH
22 0620
Dir. of Survey
Upstream
Length Surveyed
460.2 ft.
Total Length
460.2 ft.
Structural Index
3
Structural Quick
3Q00
Structural Rating
273
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
273
Pipe schematic from manhole 22 0619 to 22 0620
MH: 22 0619MH: 22 0620upstream0 ft. AMH - Upstream Manhole, Survey Ends - 22 06200 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish27.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"75 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"96.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"120.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"144.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"163.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"197.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"221.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"249.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"274.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"294.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"321.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"374.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"387.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"423.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"452.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"457.2 ft. MGO - General Observation - MAG COAT457.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start460.2 ft. AMH - Downstream Manhole, Survey Begins - 22 0619460.2 ft. MWM - Water Mark, 20 %of cross sectional area460.2 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (1)

  • General Observation - MAG COAT

    3 ft. - General Observation - MAG COAT

Observations (24)

DistanceCodeObservation
8TF
72.6TFA
460.2AMH22 0620
363.9TFC
262.5TFC
432.8TFC
166.1TF
296.4TF
210.5TFC
457.2SAV
0AMH22 0619
315.4TF
185.9TFC
36.3TFC
86TFC
138.5TFC
3MGOMAG COAT
339.9TFC
238.3TFC
385.2TFC
460.2MGOCONNECTION AT THE MH 3 OC'LOCK
0MWM
2.4SAV
0MWL

Properties (7)

additional_info
630074042522201
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-04-26T02:28:37-07:00
documentation
PROPIPE
is_lateral_inspection
false