Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 21, 2022, 10:00 AM
  • 22 0681_22 0680_04212022_042210.mp4

Date
04/21/2022
W/O
951828
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00827
PipeID
P17031
Time
3:00 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10077
Sewer Name
22 SUNFLOWER TRUNK
City
SAN DIMAS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
15
Purpose
Routine Assessment
Project
RFIR_WO_951828_TV22166_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 0681
Downstream MH
22 0680
Dir. of Survey
Downstream
Length Surveyed
374.8 ft.
Total Length
374.8 ft.
Structural Index
3
Structural Quick
3N22
Structural Rating
229
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
229
Pipe schematic from manhole 22 0681 to 22 0680
MH: 22 0681MH: 22 0680downstream0 ft. MGO - General Observation - CONNECTION AT MH 6 O'CLOCK0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 06812.1 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start68.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"94.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"148.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"167 ft. SSS - Surface Spalling, from 11 to 12 o'clock, within 8 inches of joint: NO177.1 ft. SSS - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: NO210.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"226.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"302.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"363.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"373.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"374.8 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish374.8 ft. AMH - Downstream Manhole, Survey Ends - 22 0680

Observation photos (1)

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
0MGOCONNECTION AT MH 6 O'CLOCK
0MWL
210.7TFC
167SSS
0MWM
373.4TFC
0AMH22 0681
374.8SAV
302.4TFC
68.6TF
177.1SSS
374.8AMH22 0680
363.6TFC
226.4TFC
94.1TFC
2.1SAV
148.3TFA

Properties (7)

additional_info
630098042022201
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-04-21T03:00:51-07:00
documentation
PROPIPE
is_lateral_inspection
false