Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 21, 2022, 09:10 AM
  • 22 0652_22 0651_04212022_032533.mp4

Date
04/21/2022
W/O
951828
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00827
PipeID
P17000
Time
2:10 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10077
Sewer Name
22 SUNFLOWER TRUNK
City
GLENDORA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_951828_TV22166_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0651
Downstream MH
22 0652
Dir. of Survey
Upstream
Length Surveyed
339.4 ft.
Total Length
339.4 ft.
Structural Index
3
Structural Quick
3L2K
Structural Rating
325
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
325
Pipe schematic from manhole 22 0651 to 22 0652
MH: 22 0651MH: 22 0652upstream0 ft. AMH - Upstream Manhole, Survey Ends - 22 06522.1 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish27.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"39.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"64.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"88.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"138.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"166.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"191.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"251.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"257.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"313.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start335.5 ft. MGO - General Observation - MAG COATING335.5 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start339.4 ft. AMH - Downstream Manhole, Survey Begins - 22 0651339.4 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK339.4 ft. MWM - Water Mark, 20 %of cross sectional area339.4 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (1)

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
251TF
0AMH22 0651
3.9MGOMAG COATING
312.3TF
337.3SAV
275.1TF
201TF
82TFC
337.3SSS
0MGOCONNECTION AT MH 9 O'CLOCK
0MWM
147.6TF
173TF
299.7TF
0MWL
339.4AMH22 0652
87.5TF
3.9SAV
26SSS

Properties (7)

additional_info
630098042022201
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-04-21T02:10:29-07:00
documentation
PROPIPE
is_lateral_inspection
false