Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 21, 2022, 08:57 AM
  • 22 0651_22 0650_04212022_031021.mp4

Date
04/21/2022
W/O
951828
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00827
PipeID
P16999
Time
1:57 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10077
Sewer Name
22 SUNFLOWER TRUNK
City
GLENDORA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_951828_TV22166_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0650
Downstream MH
22 0651
Dir. of Survey
Upstream
Length Surveyed
318.9 ft.
Total Length
318.9 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
189
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
189
Pipe schematic from manhole 22 0650 to 22 0651
MH: 22 0650MH: 22 0651upstream0 ft. AMH - Upstream Manhole, Survey Ends - 22 06510 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK2.7 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish102.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"177.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"181.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"304.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"308.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"316.9 ft. MGO - General Observation - MAG COATING316.9 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start318.9 ft. AMH - Downstream Manhole, Survey Begins - 22 0650318.9 ft. MWM - Water Mark, 20 %of cross sectional area318.9 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (1)

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
0AMH22 0650
216.1TFC
10.6TFC
316.2SAV
2MGOMAG COATING
0MWM
141.7TF
14.8TFC
318.9AMH22 0651
318.9MGOCONNECTION AT MH 9 O'CLOCK
137.5TFC
0MWL
2SAV

Properties (7)

additional_info
630098042022201
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-04-21T01:57:20-07:00
documentation
PROPIPE
is_lateral_inspection
false