Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 10, 2022, 08:13 AM
  • 15 0155_15 0154_05102022_023551.mp4

Date
05/10/2022
W/O
952081
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00635
PipeID
P12056
Time
1:13 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10104
Sewer Name
15 TYLER AVENUE RELIEF TRUNK
City
EL MONTE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Routine Assessment
Project
RFIR_WO_952081_TV15235_MAY2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
15 0155
Downstream MH
15 0154
Dir. of Survey
Downstream
Length Surveyed
490.7 ft.
Total Length
490.7 ft.
Structural Index
3
Structural Quick
3R00
Structural Rating
291
O&M Index
2
O&M Quick
2R00
O&M Rating
194
Overall Index
3
Overall Quick
Overall Rating
485
Pipe schematic from manhole 15 0155 to 15 0154
MH: 15 0155MH: 15 0154downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 01550 ft. MGO - General Observation - COCKROACHES AT MH2 ft. MGO - General Observation - MAG COAT2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start100.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"488.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish488.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish490.7 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK.490.7 ft. MGO - General Observation - COCKROACHES AT MH.490.7 ft. AMH - Downstream Manhole, Survey Ends - 15 0154

Observation photos (4)

  • General Observation - COCKROACHES AT MH

    0 ft. - General Observation - COCKROACHES AT MH

  • General Observation - MAG COAT

    2 ft. - General Observation - MAG COAT

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
2MGOMAG COAT
2SAP
490.7MGOACTIVE CONNECTION AT MH 3 O'CLOCK.
2DAGS
0MWM
100.8TFA
490.7MGOCOCKROACHES AT MH.
0MWL
488.6DAGS
0AMH15 0155
488.6SAP
0MGOCOCKROACHES AT MH
490.7AMH15 0154

Properties (7)

additional_info
630063050922203
custom_field_three
SURFACE AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2022-05-10T01:13:29-07:00
documentation
PRO PIPE
is_lateral_inspection
false