Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 20, 2022, 07:57 AM
  • 01 0957_01 0956_05202022_020733.mp4

Date
05/20/2022
W/O
952113
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00228
PipeID
P01794
Time
12:57 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10120
Sewer Name
01 WRIGHT ROAD TRUNK
City
BELL
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_952113_TV01251_MAY2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
36 in.
Upstream MH
01 0957
Downstream MH
01 0956
Dir. of Survey
Downstream
Length Surveyed
274.1 ft.
Total Length
274.2 ft.
Structural Index
2
Structural Quick
2D00
Structural Rating
46
O&M Index
2
O&M Quick
2J00
O&M Rating
108
Overall Index
2
Overall Quick
Overall Rating
154
Pipe schematic from manhole 01 0957 to 01 0956
MH: 01 0957MH: 01 0956downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH0 ft. AMH - Upstream Manhole, Survey Begins - 01 09572 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start89.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES173.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start272 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish272.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish272.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish274 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE274 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE274.2 ft. MGO - General Observation - ROACHES @ MH274.2 ft. AMH - Downstream Manhole, Survey Ends - 01 0956

Observation photos (5)

  • General Observation - ROACHES @ MH

    0 ft. - General Observation - ROACHES @ MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    89.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    173.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • General Observation - ROACHES @ MH

    274.2 ft. - General Observation - ROACHES @ MH

Observations (15)

DistanceCodeObservation
0MWL
274.2MGOROACHES @ MH
0MWM
0MGOROACHES @ MH
272.6DAGS
2DAGS
274.2AMH01 0956
89.1CL
2SSS
272.6CL
272SSS
274MGOCONN @ MH 9 O'CLOCK/ACTIVE
173.8CL
0AMH01 0957
274MGOCONN @ MH 3 O'CLOCK/ACTIVE

Properties (8)

additional_info
630074051922201
custom_field_three
SPALLING/MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2022-05-20T00:57:14-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
10286