Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 20, 2022, 05:48 AM
  • 01 0967_01 0966_05192022_235542.mp4

Date
05/19/2022
W/O
952113
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00228
PipeID
P01804
Time
10:48 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10120
Sewer Name
01 WRIGHT ROAD TRUNK
City
BELL
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_952113_TV01251_MAY2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
33 in.
Upstream MH
01 0967
Downstream MH
01 0966
Dir. of Survey
Downstream
Length Surveyed
181.5 ft.
Total Length
181.5 ft.
Structural Index
2
Structural Quick
322F
Structural Rating
76
O&M Index
2
O&M Quick
2F00
O&M Rating
72
Overall Index
2
Overall Quick
Overall Rating
148
Pipe schematic from manhole 01 0967 to 01 0966
MH: 01 0967MH: 01 0966downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 09670 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.5 ft. FS - Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start179 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish180.1 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE180.1 ft. FS - Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish180.1 ft. MGO - General Observation - ROACHES @ MH180.1 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE180.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish181.5 ft. AMH - Downstream Manhole, Survey Ends - 01 0966

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

    5.5 ft. - Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

  • General Observation - ROACHES @ MH

    180.1 ft. - General Observation - ROACHES @ MH

Observations (13)

DistanceCodeObservation
180.1MGOCONN @ MH 3 O'CLOCK/ACTIVE
0AMH01 0967
5.5FS
180.1FS
2DAGS
2SSS
0MWL
181.5AMH01 0966
179SSS
180.1MGOROACHES @ MH
0MWM
180.1MGOCONN @ MH 9 O'CLOCK/ACTIVE
180.1DAGS

Properties (8)

additional_info
630074051922201
custom_field_three
CONTINUOUS FRACTURES
custom_field_two
2
customer
1
datetime
2022-05-19T22:48:30-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
10286