Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 20, 2022, 09:00 AM
  • 01 0962_01 0961_05202022_031051.mp4

Date
05/20/2022
W/O
952113
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00228
PipeID
P01799
Time
2:00 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10120
Sewer Name
01 WRIGHT ROAD TRUNK
City
BELL
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_952113_TV01251_MAY2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
33 in.
Upstream MH
01 0962
Downstream MH
01 0961
Dir. of Survey
Downstream
Length Surveyed
325 ft.
Total Length
325 ft.
Structural Index
2
Structural Quick
2R00
Structural Rating
190
O&M Index
2
O&M Quick
2L00
O&M Rating
128
Overall Index
2
Overall Quick
Overall Rating
318
Pipe schematic from manhole 01 0962 to 01 0961
MH: 01 0962MH: 01 0961downstream0 ft. MGO - General Observation - ROACHES @ MH0 ft. AMH - Upstream Manhole, Survey Begins - 01 09620 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start168.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start322 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish322.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish322.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish324.9 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE324.9 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE325 ft. AMH - Downstream Manhole, Survey Ends - 01 0961325 ft. MGO - General Observation - ROACHES@ MH

Observation photos (4)

  • General Observation - ROACHES @ MH

    0 ft. - General Observation - ROACHES @ MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    168.6 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • General Observation - ROACHES@ MH

    325 ft. - General Observation - ROACHES@ MH

Observations (14)

DistanceCodeObservation
2DAGS
168.6CL
0MGOROACHES @ MH
0AMH01 0962
322.9DAGS
325AMH01 0961
322SSS
0MWM
0MWL
324.9MGOCONN @ MH 9 O'CLOCK/ACTIVE
322.9CL
2SSS
325MGOROACHES@ MH
324.9MGOCONN @ MH 3 O'CLOCK/ACTIVE

Properties (8)

additional_info
630074051922201
custom_field_three
MULTIPLE CONTINUOUS FRACTURES
custom_field_two
2
customer
1
datetime
2022-05-20T02:00:28-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
10286