Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 10, 2022, 05:29 AM
  • 18 0288_18 0287_05092022_234335.mp4

Date
05/09/2022
W/O
952141
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00702
PipeID
P14117
Time
10:29 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10093
Sewer Name
18 SHOEMAKER AVENUE TRUNK
City
SANTA FE SPRINGS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
30
Purpose
Routine Assessment
Project
RFIR_WO_952141_TV18148_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0288
Downstream MH
18 0287
Dir. of Survey
Downstream
Length Surveyed
291.5 ft.
Total Length
291.5 ft.
Structural Index
3
Structural Quick
433K
Structural Rating
299
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
299
Pipe schematic from manhole 18 0288 to 18 0287
MH: 18 0288MH: 18 0287downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 02880 ft. MWL - Water Level, 10 %of cross sectional area2.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6", 6"15.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start52.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"53.6 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES55.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"75.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES104.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"107.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"115.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES153.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"156.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"203.4 ft. CM - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES205.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"207.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"224.7 ft. CM - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES253.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"256.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"288.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish288.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish291.5 ft. AMH - Downstream Manhole, Survey Ends - 18 0287

Observation photos (7)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    15.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    53.6 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    75.3 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    115.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

    203.4 ft. - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

    224.7 ft. - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

Observations (24)

DistanceCodeObservation
203.4CM
253.7TFC
55.3TFC
153.1TFC
15.6SSS
53.6FM
0MWM
256.5TFC
115.1FM
52.2TFC
104.5TFC
0AMH18 0288
288.4SSS
3.5TFC
291.5AMH18 0287
107.4TFC
156.5TFC
224.7CM
205.2TFC
0MWL
207.6TFC
75.3FM
288.4SAV
2.4SAV

Properties (7)

additional_info
630074050922201
custom_field_three
AGGREGATE VISIBLE/SURFACE SPALLING
custom_field_two
3
customer
1
datetime
2022-05-09T22:29:11-07:00
documentation
PROPIPE
is_lateral_inspection
false