Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 10, 2022, 08:34 AM
  • 18 0276_18 0275_05102022_024622.mp4

Date
05/10/2022
W/O
952141
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00702
PipeID
P14104
Time
1:34 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10093
Sewer Name
18 SHOEMAKER AVENUE TRUNK
City
SANTA FE SPRINGS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
30
Purpose
Routine Assessment
Project
RFIR_WO_952141_TV18148_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0276
Downstream MH
18 0275
Dir. of Survey
Downstream
Length Surveyed
209.2 ft.
Total Length
209.2 ft.
Structural Index
3
Structural Quick
3G00
Structural Rating
123
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
123
Pipe schematic from manhole 18 0276 to 18 0275
MH: 18 0276MH: 18 0275downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 02763.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start28.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"31.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"76.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"79.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"127.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"128.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"131 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"176.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"179.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"206 ft. MGO - General Observation - SURFACE SPALLING THROUGHOUT, FROM 9 TO 3 OCLOCK,206.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish209.2 ft. AMH - Downstream Manhole, Survey Ends - 18 0275209.2 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
76.6TFC
28.1TFC
31.2TFC
0MWL
209.2AMH18 0275
176.3TFC
179.2TFC
206.4SAV
0MWM
131TFC
79.6TF
3.3SAV
206MGOSURFACE SPALLING THROUGHOUT, FROM 9 TO 3 OCLOCK,
128.3TF
209.2MGOCONNECTION AT THE MH 3 OC'LOCK
0AMH18 0276
127.6TFC

Properties (7)

additional_info
630074050922201
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-05-10T01:34:17-07:00
documentation
PROPIPE
is_lateral_inspection
false