Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 10, 2022, 08:56 AM
  • 18 0274_18 0273_05102022_031413.mp4

Date
05/10/2022
W/O
952141
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00702
PipeID
P14102
Time
1:56 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10093
Sewer Name
18 SHOEMAKER AVENUE TRUNK
City
SANTA FE SPRINGS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
30
Purpose
Routine Assessment
Project
RFIR_WO_952141_TV18148_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0274
Downstream MH
18 0273
Dir. of Survey
Downstream
Length Surveyed
365.9 ft.
Total Length
365.9 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
216
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
216
Pipe schematic from manhole 18 0274 to 18 0273
MH: 18 0274MH: 18 0273downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 02740 ft. MWM - Water Mark, 20 %of cross sectional area2.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start16.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"19.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"65.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"68.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"116.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"119.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"167.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"171 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"213.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"216.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"265.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"267.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"316.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"319.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"363 ft. MGO - General Observation - SURFACE SPALLING THROUGHOUT THE REACH, FROM 9 TO 3 OCLOCK363.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish365.9 ft. AMH - Downstream Manhole, Survey Ends - 18 0273365.9 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK365.9 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.9 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
119.4TF
2.9SAV
19.8TFC
16.9TFC
365.9AMH18 0273
0MWL
319.3TFC
213.3TFC
171TFC
267.9TF
365.9MGOCONNECTION AT THE MH 9 OC'LOCK
0AMH18 0274
0MWM
65.3TFA
167.8TFC
363.1SAV
365.9MGOCONNECTION AT THE MH 3 OC'LOCK
363MGOSURFACE SPALLING THROUGHOUT THE REACH, FROM 9 TO 3 OCLOCK
68.1TFC
316.5TFC
116.6TFC
216.2TFC
265.1TFC

Properties (7)

additional_info
630074050922201
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-05-10T01:56:37-07:00
documentation
PROPIPE
is_lateral_inspection
false