Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 11, 2022, 08:59 AM
  • H 1195_H 0580_05112022_033550.mp4

Date
05/11/2022
W/O
951821
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00188
PipeID
P21382
Time
1:59 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10107
Sewer Name
H JOINT OUTFALL H - UNIT 8E
City
BALDWIN PARK
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_951821_TV15172_MAY2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
H 1195
Downstream MH
H 0580
Dir. of Survey
Downstream
Length Surveyed
199 ft.
Total Length
199 ft.
Structural Index
3
Structural Quick
5G3G
Structural Rating
390
O&M Index
2
O&M Quick
412G
O&M Rating
82
Overall Index
3
Overall Quick
Overall Rating
472
Pipe schematic from manhole H 1195 to H 0580
MH: H 1195MH: H 0580downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 11952 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start196.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish196.7 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish196.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish196.7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish199 ft. MGO - General Observation - MOBILE MMS - 200.86'.199 ft. MGO - General Observation - COCKROACHES AT MH199 ft. AMH - Downstream Manhole, Survey Ends - H 0580, RUN LIST STATES MH AT 351'.199 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (5)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES AT MH

    199 ft. - General Observation - COCKROACHES AT MH

Observations (16)

DistanceCodeObservation
196.7DAGS
199MGOMOBILE MMS - 200.86'.
196.7SRV
0MGOCONNECTION AT MH 3 O'CLOCK
196.7SSS
199MGOCOCKROACHES AT MH
199AMHH 0580, RUN LIST STATES MH AT 351'.
196.7SAP
2SAP
0MWL
2SRV
2SSS
2DAGS
199MGOCONNECTION AT MH 3 O'CLOCK
0MWM
0AMHH 1195

Properties (7)

additional_info
630063051022203
custom_field_three
VISIBLE REINFORCEMENT/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2022-05-11T01:59:54-07:00
documentation
PRO PIPE
is_lateral_inspection
false