Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 5, 2022, 09:30 AM
  • 18 0099_18 0098_05052022_034123.mp4

Date
05/05/2022
W/O
951925
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13919
Time
2:30 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10090
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_951925_TV18083_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0099
Downstream MH
18 0098
Dir. of Survey
Downstream
Length Surveyed
195.9 ft.
Total Length
195.9 ft.
Structural Index
3
Structural Quick
3B22
Structural Rating
49
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
49
Pipe schematic from manhole 18 0099 to 18 0098
MH: 18 0099MH: 18 0098downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 00990 ft. MWL - Water Level, 10 %of cross sectional area2.6 ft. MMC - Material Change, Vitrified clay pipe24.5 ft. CM - Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES42 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"53.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES62.7 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES66 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"102.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"103.6 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES114.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES130.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"137 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES141.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start188.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"195.9 ft. MGO - General Observation - CONNECTION AT THE MH 12 OC'LOCK195.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish195.9 ft. AMH - Downstream Manhole, Survey Ends - 18 0098

Observation photos (8)

  • Material Change, Vitrified clay pipe

    2.6 ft. - Material Change, Vitrified clay pipe

  • Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

    24.5 ft. - Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    53.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    62.7 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

    103.6 ft. - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    114.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    137 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    141.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
24.5CM
0MWM
195.9MGOCONNECTION AT THE MH 12 OC'LOCK
130.4TF
42TF
0AMH18 0099
102.8TF
103.6CL
114.4CM
141.6CM
137CM
53.9CM
188.3TF
195.9CM
195.9AMH18 0098
66TF
0MWL
62.7CL
2.6MMC

Properties (7)

additional_info
630074050422202
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2022-05-05T02:30:33-07:00
documentation
PROPIPE
is_lateral_inspection
false