Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 2, 2022, 08:04 AM
  • 18 0095_18 0094_05022022_022753.mp4

Date
05/02/2022
W/O
951925
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13915
Time
1:04 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10085
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_951925_TV18083_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Square
Height
15 in.
Width
15 in.
Upstream MH
18 0095
Downstream MH
18 0094
Dir. of Survey
Downstream
Length Surveyed
285.1 ft.
Total Length
285.1 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
171
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
171
Pipe schematic from manhole 18 0095 to 18 0094
MH: 18 0095MH: 18 0094downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 00950 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.4 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"134.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"197.8 ft. TS - Tap Saddle, at 01 o'clock, -, within 8 inches of joint: NO, 6"285.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish285.1 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK285.1 ft. AMH - Downstream Manhole, Survey Ends - 18 0094

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Saddle, at 01 o'clock, -, within 8 inches of joint: NO, 6"

    197.8 ft. - Tap Saddle, at 01 o'clock, -, within 8 inches of joint: NO, 6"

Observations (10)

DistanceCodeObservation
7.4TFC
285.1SAV
134.2TFC
0AMH18 0095
0MWL
2.3SAV
285.1MGOCONNECTION AT THE MH 3 OC'LOCK
197.8TS
285.1AMH18 0094
0MWM

Properties (7)

additional_info
630074050222001
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-05-02T01:04:13-07:00
documentation
PROPIPE
is_lateral_inspection
false