Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 2, 2022, 11:00 AM
  • 18 0086_18 0085_05022022_051233.mp4

Date
05/02/2022
W/O
951925
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13905
Time
4:00 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10085
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_951925_TV18083_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0086
Downstream MH
18 0085
Dir. of Survey
Downstream
Length Surveyed
311.6 ft.
Total Length
311.6 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
189
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
189
Pipe schematic from manhole 18 0086 to 18 0085
MH: 18 0086MH: 18 0085downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 00863 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11.6 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES112.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"212.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"286.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES308.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish311.6 ft. AMH - Downstream Manhole, Survey Ends - 18 0085

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    11.6 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    286.5 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
0MGOCONNECTION AT THE MH 3 OC'LOCK
0MWL
212.3TFC
286.5FL
112.3TFC
0MWM
308.6SAV
11.6FL
0AMH18 0086
311.6AMH18 0085
3SAV

Properties (7)

additional_info
630074050222001
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-05-02T04:00:23-07:00
documentation
PROPIPE
is_lateral_inspection
false