Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 27, 2022, 06:26 AM
  • 18 0119_18 0118_04272022_004046.mp4

Date
04/26/2022
W/O
951925
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13940
Time
11:26 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10081
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_951925_TV18083_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0119
Downstream MH
18 0118
Dir. of Survey
Downstream
Length Surveyed
357.5 ft.
Total Length
357.5 ft.
Structural Index
3
Structural Quick
3N00
Structural Rating
219
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
219
Pipe schematic from manhole 18 0119 to 18 0118
MH: 18 0119MH: 18 0118downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 01192.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start18.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"24.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"41.4 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES52.9 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES69.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"75.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"121.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"127 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"167.9 ft. MGO - General Observation - POINT REPAIR169.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"175.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"220.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"226.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"269.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"275.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"320.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"326.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"354.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish357.5 ft. AMH - Downstream Manhole, Survey Ends - 18 0118

Observation photos (4)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    41.4 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    52.9 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • General Observation - POINT REPAIR

    167.9 ft. - General Observation - POINT REPAIR

Observations (23)

DistanceCodeObservation
121.1TF
0MWL
275.3TFC
167.9MGOPOINT REPAIR
52.9CM
357.5AMH18 0118
75.8TFC
127TFC
354.7SAV
320.3TFC
0MWM
175.5TFC
0AMH18 0119
18.2TF
326.4TFC
220.9TF
169.4TF
226.7TFC
41.4FL
24.3TFC
2.1SAV
69.9TFC
269.1TF

Properties (7)

additional_info
630074042622201
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-04-26T23:26:12-07:00
documentation
PROPIPE
is_lateral_inspection
false