Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 27, 2022, 06:49 AM
  • 18 0987_18 0117_04272022_005819.mp4

Date
04/26/2022
W/O
951925
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13938
Time
11:49 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10081
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_951925_TV18083_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0987
Downstream MH
18 0117
Dir. of Survey
Downstream
Length Surveyed
175.4 ft.
Total Length
175.4 ft.
Structural Index
3
Structural Quick
3F00
Structural Rating
105
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
105
Pipe schematic from manhole 18 0987 to 18 0117
MH: 18 0987MH: 18 0117downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 09872.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start32 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"38.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"39.7 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES83.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"89.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"134.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"140.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"162 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"167.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"172.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish175.4 ft. AMH - Downstream Manhole, Survey Ends - 18 0117

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    39.7 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

Observations (16)

DistanceCodeObservation
140.9TFC
2.4SAV
32TFC
0MWM
0MGOCONNECTION AT THE MH 9 OC'LOCK
83.4TF
0MWL
175.4AMH18 0117
162TFC
134.8TF
39.7FL
89.4TFC
0AMH18 0987
172.6SAV
167.9TFC
38.1TFC

Properties (7)

additional_info
630074042622201
custom_field_three
AGGREGATE VISIBLE/FRACTURE
custom_field_two
3
customer
1
datetime
2022-04-26T23:49:37-07:00
documentation
PROPIPE
is_lateral_inspection
false