Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 27, 2022, 09:05 AM
  • 18 0114_18 0113_04272022_031217.mp4

Date
04/27/2022
W/O
951925
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13934
Time
2:05 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10081
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_951925_TV18083_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0114
Downstream MH
18 0113
Dir. of Survey
Downstream
Length Surveyed
109.3 ft.
Total Length
109.3 ft.
Structural Index
3
Structural Quick
3F00
Structural Rating
108
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
108
Pipe schematic from manhole 18 0114 to 18 0113
MH: 18 0114MH: 18 0113downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 01140 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area2.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"11.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"31.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start50.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"57.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"99.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"106.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish106.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"106.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish109.3 ft. AMH - Downstream Manhole, Survey Ends - 18 0113109.3 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    31.5 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
99.9TF
50.9TF
0AMH18 0114
57.4TF
106.1FL
109.3AMH18 0113
106.1TFC
31.5FL
0MWM
11.5TF
0MWL
106.1SAV
5.5TF
2.6SAV
109.3MGOCONNECTION AT THE MH 3 OC'LOCK

Properties (7)

additional_info
630074042622201
custom_field_three
AGGREGATE VISIBLE/FRACTURE'S
custom_field_two
3
customer
1
datetime
2022-04-27T02:05:38-07:00
documentation
PROPIPE
is_lateral_inspection