Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 27, 2022, 04:57 AM
  • 18 0112_18 0111_04262022_230247.mp4

Date
04/26/2022
W/O
951925
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13932
Time
9:57 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10081
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_951925_TV18083_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0112
Downstream MH
18 0111
Dir. of Survey
Downstream
Length Surveyed
60.4 ft.
Total Length
60.4 ft.
Structural Index
3
Structural Quick
3B00
Structural Rating
39
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
39
Pipe schematic from manhole 18 0112 to 18 0111
MH: 18 0112MH: 18 0111downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 01120 ft. MWM - Water Mark, 20 %of cross sectional area3.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start9.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"15 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"23.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES38.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES45.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"51.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"57.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish60.4 ft. AMH - Downstream Manhole, Survey Ends - 18 011160.4 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    23.2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    38.2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
57.9SAV
38.2FL
15TF
60.4AMH18 0111
45.4TFC
0MWL
0AMH18 0112
0MWM
3.9SAV
9.1TF
51.7TFC
60.4MGOCONNECTION AT THE MH 3 OC'LOCK
23.2FL

Properties (7)

additional_info
630074042622201
custom_field_three
AGGREGATE VISIBLE/FRACTURE'S
custom_field_two
3
customer
1
datetime
2022-04-26T21:57:21-07:00
documentation
PROPIPE
is_lateral_inspection
false