Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 27, 2022, 05:15 AM
  • 18 0110_18 0109_04262022_231932.mp4

Date
04/26/2022
W/O
951925
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13930
Time
10:15 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10081
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_951925_TV18083_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0110
Downstream MH
18 0109
Dir. of Survey
Downstream
Length Surveyed
41.6 ft.
Total Length
41.6 ft.
Structural Index
3
Structural Quick
3900
Structural Rating
27
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
27
Pipe schematic from manhole 18 0110 to 18 0109
MH: 18 0110MH: 18 0109downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 01100 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK CAPPED0 ft. MWL - Water Level, 15 %of cross sectional area2.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start18.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES32.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"38.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"39.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish41.6 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK41.6 ft. AMH - Downstream Manhole, Survey Ends - 18 0109

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    18.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
2.3SAV
18.9FL
0MWM
0AMH18 0110
0MGOCONNECTION AT THE MH 3 OC'LOCK CAPPED
41.6MGOCONNECTION AT THE MH 3 OC'LOCK
0MWL
41.6AMH18 0109
39.9SAV
38.9TFC
32.4TF

Properties (7)

additional_info
630074042622201
custom_field_three
AGGREGATE VISIBLE/FRACTURE'S
custom_field_two
3
customer
1
datetime
2022-04-26T22:15:39-07:00
documentation
PROPIPE
is_lateral_inspection
false