Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 27, 2022, 05:19 AM
  • 18 0109_18 0108_04262022_233416.mp4

Date
04/26/2022
W/O
951925
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13929
Time
10:19 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10081
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_951925_TV18083_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0109
Downstream MH
18 0108
Dir. of Survey
Downstream
Length Surveyed
266.2 ft.
Total Length
266.2 ft.
Structural Index
3
Structural Quick
3R00
Structural Rating
282
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
282
Pipe schematic from manhole 18 0109 to 18 0108
MH: 18 0109MH: 18 0108downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 01090 ft. MWL - Water Level, 15 %of cross sectional area2.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start14.3 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES23.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES39.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"46.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"66.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start91.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"98.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"140.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"146.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"189.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"195.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"241.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"247.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"264.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish264.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish266.2 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK266.2 ft. AMH - Downstream Manhole, Survey Ends - 18 0108

Observation photos (4)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    14.3 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    23.5 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    66.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

Observations (22)

DistanceCodeObservation
195.6TFC
189.6TF
66.1FL
241.4TFC
0MGOCONNECTION AT THE MH 3 OC'LOCK
91.8TF
266.2MGOCONNECTION AT THE MH 3 OC'LOCK
98.2TFC
39.8TF
247.2TFC
14.3FL
2.5SAV
266.2AMH18 0108
23.5FL
264.3SAV
0MWM
140.4TF
264.3FL
46.1TFC
0AMH18 0109
0MWL
146.9TFC

Properties (7)

additional_info
630074042622201
custom_field_three
AGGREGATE VISIBLE/FRACTURE'S
custom_field_two
3
customer
1
datetime
2022-04-26T22:19:42-07:00
documentation
PROPIPE
is_lateral_inspection
false