Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 2, 2022, 10:48 AM
  • 18 1248_18 0086_05022022_045911.mp4

Date
05/02/2022
W/O
951925
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13906
Time
3:48 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10085
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_951925_TV18083_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 1248
Downstream MH
18 0086
Dir. of Survey
Downstream
Length Surveyed
309.8 ft.
Total Length
309.8 ft.
Structural Index
3
Structural Quick
3K21
Structural Rating
185
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
185
Pipe schematic from manhole 18 1248 to 18 0086
MH: 18 1248MH: 18 0086downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Begins - 18 12480 ft. MWM - Water Mark, 25 %of cross sectional area2.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start76.2 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES110.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"210.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"307.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish309.8 ft. AMH - Downstream Manhole, Survey Ends - 18 0086309.8 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    76.2 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
309.8AMH18 0086
307.5SAV
0MWL
0MGOCONNECTION AT THE MH 9 OC'LOCK
0AMH18 1248
2.7SAV
76.2CL
210.3TFC
309.8MGOCONNECTION AT THE MH 3 OC'LOCK
110.6TFC
0MWM

Properties (7)

additional_info
630074050222001
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-05-02T03:48:15-07:00
documentation
PROPIPE
is_lateral_inspection
false