Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 26, 2022, 09:04 AM
  • 18 0280_18 0279_04262022_042505.mp4

Date
04/26/2022
W/O
951554
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00702
PipeID
P14108
Time
2:04 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9971
Sewer Name
18 SHOEMAKER AVENUE TRUNK
City
NORWALK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
30
Purpose
Routine Assessment
Project
RFIR_WO_951554_TV18178_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0279
Downstream MH
18 0280
Dir. of Survey
Upstream
Length Surveyed
300.4 ft.
Total Length
300.4 ft.
Structural Index
3
Structural Quick
3K2K
Structural Rating
300
O&M Index
2
O&M Quick
2K00
O&M Rating
120
Overall Index
2
Overall Quick
Overall Rating
420
Pipe schematic from manhole 18 0279 to 18 0280
MH: 18 0279MH: 18 0280upstream0 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish0 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. MSA - Survey Abandoned - COMPLETED REVERSAL ZOOMED IN2.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"5.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"53.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"57.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"105.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"109.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"155.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"157.3 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"157.3 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"206.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"210.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"259.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"262.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"298.4 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start298.4 ft. MGO - General Observation - MAG COATING298.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start298.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start300.4 ft. MWL - Water Level, 10 %of cross sectional area300.4 ft. AMH - Downstream Manhole, Survey Begins - 18 0279300.4 ft. MWM - Water Mark, 30 %of cross sectional area

Observation photos (5)

  • General Observation - MAG COATING

    2 ft. - General Observation - MAG COATING

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"

    143.1 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    143.1 ft. - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (24)

DistanceCodeObservation
242.7TFC
300.4DSC
143.1TB
0MWL
246.6TFC
2DSC
90.2TFC
2MGOMAG COATING
0AMH18 0279
294.9TFC
194.9TFC
143.1TBA
300.4SAV
2SSS
190.6TFC
300.4SSS
38.1TFC
144.9TFC
298.2TFC
93.7TFC
0MWM
41.2TFC
2SAV
300.4MSACOMPLETED REVERSAL ZOOMED IN

Properties (7)

additional_info
630098042522201
custom_field_three
SPALLING, AGGREGATE VISBLE, FINE DEBRIS
custom_field_two
2
customer
1
datetime
2022-04-26T02:04:15-07:00
documentation
PRO PIPE
is_lateral_inspection
false