Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 26, 2022, 06:15 AM
  • 18 0284_18 0283_04262022_003553.mp4

Date
04/25/2022
W/O
951554
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00702
PipeID
P14112
Time
11:15 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9971
Sewer Name
18 SHOEMAKER AVENUE TRUNK
City
NORWALK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
30
Purpose
Routine Assessment
Project
RFIR_WO_951554_TV18178_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0284
Downstream MH
18 0283
Dir. of Survey
Downstream
Length Surveyed
332.7 ft.
Total Length
332.7 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
330
O&M Index
2
O&M Quick
2L00
O&M Rating
132
Overall Index
2
Overall Quick
Overall Rating
462
Pipe schematic from manhole 18 0284 to 18 0283
MH: 18 0284MH: 18 0283downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 02840 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED2 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEPOSITS / OTHER INFERRED - NOT SEEN DURING VIDEO OBSERVATIONS - TRACTOR "BOUNCING".2.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.5 ft. MGO - General Observation - MAG COATING28.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"30.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"76.1 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"79 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"125.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"128.6 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"180.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"183.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"229.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"232.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"281.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"283.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"332 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish - DEPOSITS / OTHER INFERRED - NOT SEEN DURING VIDEO OBSERVATIONS - TRACTOR "BOUNCING".332.7 ft. MGO - General Observation - ACTIVE CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK332.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish332.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish332.7 ft. AMH - Downstream Manhole, Survey Ends - 18 0283

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COATING

    2.5 ft. - General Observation - MAG COATING

Observations (25)

DistanceCodeObservation
2DSZDEPOSITS / OTHER INFERRED - NOT SEEN DURING VIDEO OBSERVATIONS - TRACTOR "BOUNCING".
2.5SAV
281.7TFC
79TFC
332DSZDEPOSITS / OTHER INFERRED - NOT SEEN DURING VIDEO OBSERVATIONS - TRACTOR "BOUNCING".
125.2TFC
0AMH18 0284
283.9TFC
183.7TFC
332.7MGOACTIVE CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK
76.1TFC
2.5SSS
229.5TFC
180.5TFC
0MWM
232.2TFC
28.3TFC
0MWL
332.7SAV
30.2TFC
0MGOCONNECTION AT MH 9 O'CLOCK CAPPED
332.7SSS
2.5MGOMAG COATING
128.6TFC
332.7AMH18 0283

Properties (7)

additional_info
630098042522201
custom_field_three
SPALLING, AGGREGATE VISBLE
custom_field_two
2
customer
1
datetime
2022-04-25T23:15:59-07:00
documentation
PRO PIPE
is_lateral_inspection
false