Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 26, 2022, 06:36 AM
  • 18 0283_18 0282_04262022_005846.mp4

Date
04/25/2022
W/O
951554
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00702
PipeID
P14111
Time
11:36 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9971
Sewer Name
18 SHOEMAKER AVENUE TRUNK
City
NORWALK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
30
Purpose
Routine Assessment
Project
RFIR_WO_951554_TV18178_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0283
Downstream MH
18 0282
Dir. of Survey
Downstream
Length Surveyed
356.4 ft.
Total Length
356.4 ft.
Structural Index
3
Structural Quick
3M2M
Structural Rating
355
O&M Index
2
O&M Quick
2M00
O&M Rating
142
Overall Index
2
Overall Quick
Overall Rating
497
Pipe schematic from manhole 18 0283 to 18 0282
MH: 18 0283MH: 18 0282downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 18 02830 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEPOSITS / OTHER INFERRED - NOT SEEN DURING VIDEO OBSERVATIONS - TRACTOR "BOUNCING".2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start53.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"56.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"102.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"105.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"154.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"156.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"205.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"208.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"253.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"257 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"305.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"308.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"355 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish - DEPOSITS / OTHER INFERRED - NOT SEEN DURING VIDEO OBSERVATIONS - TRACTOR "BOUNCING".355.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish355.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish356.4 ft. AMH - Downstream Manhole, Survey Ends - 18 0282

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
53.5TFC
56.5TFC
205.3TFC
2.1SSS
355.5SSS
154.3TFC
0MWL
208.5TFC
355DSZDEPOSITS / OTHER INFERRED - NOT SEEN DURING VIDEO OBSERVATIONS - TRACTOR "BOUNCING".
356.4AMH18 0282
305.7TFC
257TFC
2.1SAV
2DSZDEPOSITS / OTHER INFERRED - NOT SEEN DURING VIDEO OBSERVATIONS - TRACTOR "BOUNCING".
0MGOACTIVE CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK
0AMH18 0283
308.5TF
0MWM
156.9TFC
102.2TFC
105.4TFC
355.5SAV
253.9TFC

Properties (7)

additional_info
630098042522201
custom_field_three
SPALLING, AGGREGATE VISBLE
custom_field_two
2
customer
1
datetime
2022-04-25T23:36:57-07:00
documentation
PRO PIPE
is_lateral_inspection
false