Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 11, 2022, 10:04 AM
  • 18 1087_18 1085_05112022_042406.mp4

Date
05/11/2022
W/O
951858
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00675
PipeID
P14946
Time
3:04 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10095
Sewer Name
18 FLORENCE AVENUE TRUNK
City
SANTA FE SPRINGS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_951858_TV18097_MAY2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 1085
Downstream MH
18 1087
Dir. of Survey
Upstream
Length Surveyed
403.7 ft.
Total Length
403.7 ft.
Structural Index
3
Structural Quick
3522
Structural Rating
19
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
21
Pipe schematic from manhole 18 1085 to 18 1087
MH: 18 1085MH: 18 1087upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 108749.2 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES61.3 ft. FS - Fracture Spiral, from 07 to 12 o'clock, within 8 inches of joint: YES67.5 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES73.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES117 ft. ISSRH - Intruding Sealing Ring Hanging, 5 %of cross sectional area, from 12 to 01 o'clock123.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES140.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES382 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES403.7 ft. MWL - Water Level, 15 %of cross sectional area403.7 ft. AMH - Downstream Manhole, Survey Begins - 18 1085403.7 ft. MWM - Water Mark, 20 %of cross sectional area

Observation photos (8)

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    21.7 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    263.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    280.5 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Intruding Sealing Ring Hanging, 5 %of cross sectional area, from 12 to 01 o'clock

    286.7 ft. - Intruding Sealing Ring Hanging, 5 %of cross sectional area, from 12 to 01 o'clock

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    329.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    336.2 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 07 to 12 o'clock, within 8 inches of joint: YES

    342.4 ft. - Fracture Spiral, from 07 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    354.5 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
0MWL
336.2FL
0AMH18 1085
263.1CL
0MWM
21.7FL
403.7AMH18 1087
280.5CL
329.9FL
354.5FL
342.4FS
286.7ISSRH

Properties (8)

additional_info
630074051022202
custom_field_three
MULTIPLE CRACKS/FRACTURE'S
custom_field_two
2
customer
1
datetime
2022-05-11T03:04:44-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
27555