Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 11, 2022, 07:38 AM
  • 18 0444_18 0443_05112022_020004.mp4

Date
05/11/2022
W/O
951858
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00675
PipeID
P14295
Time
12:38 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10095
Sewer Name
18 FLORENCE AVENUE TRUNK
City
SANTA FE SPRINGS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_951858_TV18097_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0444
Downstream MH
18 0443
Dir. of Survey
Downstream
Length Surveyed
291.8 ft.
Total Length
291.8 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
174
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
174
Pipe schematic from manhole 18 0444 to 18 0443
MH: 18 0444MH: 18 0443downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 04440 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start14.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"39.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"67.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"90.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"115.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"143.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"167.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"191.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"215.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"239.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"264.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"289.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish291.8 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK291.8 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK291.8 ft. AMH - Downstream Manhole, Survey Ends - 18 0443

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
90.9TFC
0AMH18 0444
0MWM
115.4TFC
239.8TFC
291.8MGOCONNECTION AT THE MH 9 OC'LOCK
289.8SAV
291.8MGOCONNECTION AT THE MH 3 OC'LOCK
291.8AMH18 0443
39.1TFC
191.9TFC
0MWL
2.1SAV
215.9TFC
14.8TFC
143.5TFC
67.1TFC
167.7TFC
264.6TFC

Properties (7)

additional_info
630074051022202
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-05-11T00:38:22-07:00
documentation
PROPIPE
is_lateral_inspection
false