Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 11, 2022, 08:33 AM
  • 18 0440_18 0439A_05112022_024259.mp4

Date
05/11/2022
W/O
951858
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00675
PipeID
P14291
Time
1:33 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10095
Sewer Name
18 FLORENCE AVENUE TRUNK
City
SANTA FE SPRINGS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_951858_TV18097_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0440
Downstream MH
18 0439A
Dir. of Survey
Downstream
Length Surveyed
205.2 ft.
Total Length
205.2 ft.
Structural Index
3
Structural Quick
3G00
Structural Rating
120
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
120
Pipe schematic from manhole 18 0440 to 18 0439A
MH: 18 0440MH: 18 0439Adownstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 04400 ft. MWL - Water Level, 10 %of cross sectional area2.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"25.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"27.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"51.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"76.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"100.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"123.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"125.3 ft. TB - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 6"152.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"176.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"202.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish205.2 ft. AMH - Downstream Manhole, Survey Ends - 18 0439A205.2 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    25.3 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 6"

    125.3 ft. - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 6"

Observations (17)

DistanceCodeObservation
205.2AMH18 0439A
51.9TFC
0MWM
7.6TFC
123.7TFC
0AMH18 0440
25.3TB
205.2MGOCONNECTION AT THE MH 3 OC'LOCK
2.6SAV
76.1TFC
125.3TB
152.5TFC
0MWL
176.4TFC
202.4SAV
100.2TF
27.7TFC

Properties (7)

additional_info
630074051022202
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-05-11T01:33:50-07:00
documentation
PROPIPE
is_lateral_inspection
false