Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 24, 2022, 07:22 AM
  • A 0433_A 0432_02232022_233203.mp4

Date
02/23/2022
W/O
936486
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00323
PipeID
P08155
Time
11:22 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9745
Sewer Name
A JOA-1A LOS COYOTES WRP INTERCEPTOR
City
SOUTH GATE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
26
Purpose
Routine Assessment
Project
RFIR_WO_936486_TV02346_FEB2022
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
63 in.
Width
39 in.
Upstream MH
A 0432
Downstream MH
A 0433
Dir. of Survey
Upstream
Length Surveyed
2 ft.
Total Length
2 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole A 0432 to A 0433
MH: A 0432MH: A 0433upstream0 ft. LFW - Lining Failure Wrinkled, from 09 to 11 o'clock, within 8 inches of joint: YES0 ft. MSA - Survey Abandoned - VIEW OF THE UP LEG OF THE DWN MH0 ft. MGO - General Observation - MAG COATING2 ft. AMH - Downstream Manhole, Survey Begins - A 04322 ft. MWM - Water Mark, 90 %of cross sectional area2 ft. MWL - Water Level, 70 %of cross sectional area

Observation photos (3)

  • Lining Failure Wrinkled, from 09 to 11 o'clock, within 8 inches of joint: YES

    2 ft. - Lining Failure Wrinkled, from 09 to 11 o'clock, within 8 inches of joint: YES

  • Survey Abandoned - VIEW OF THE UP LEG OF THE DWN MH

    2 ft. - Survey Abandoned - VIEW OF THE UP LEG OF THE DWN MH

  • General Observation - MAG COATING

    2 ft. - General Observation - MAG COATING

Observations (6)

DistanceCodeObservation
0AMHA 0432
2LFW
0MWM
2MSAVIEW OF THE UP LEG OF THE DWN MH
0MWL
2MGOMAG COATING

Properties (9)

additional_info
63009802322201
custom_field_three
WRINKLE IN LINER
custom_field_two
3
customer
1
datetime
2022-02-23T23:22:14-08:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
CIPP
year_laid
40793