Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 23, 2022, 08:45 AM
  • A 0159_A 0158_02232022_012706.mp4

Date
02/23/2022
W/O
936486
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00323
PipeID
P08096
Time
12:45 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9744
Sewer Name
A JOA-1A LOS COYOTES WRP INTERCEPTOR
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
37
Purpose
Routine Assessment
Project
RFIR_WO_936486_TV02346_FEB2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
78 in.
Width
48 in.
Upstream MH
A 0159
Downstream MH
A 0158
Dir. of Survey
Downstream
Length Surveyed
846.9 ft.
Total Length
846.9 ft.
Structural Index
3
Structural Quick
3a2a
Structural Rating
845
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
845
Pipe schematic from manhole A 0159 to A 0158
MH: A 0159MH: A 0158downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 01592 ft. MGO - General Observation - MAG COATING2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start846.9 ft. AMH - Downstream Manhole, Survey Ends - A 0158846.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish846.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • General Observation - MAG COATING

    2 ft. - General Observation - MAG COATING

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
846.9AMHA 0158
2MGOMAG COATING
0MWM
2SAV
846.9SSS
846.9SAV
0MWL
0AMHA 0159
2SSS

Properties (8)

additional_info
630098022222201
custom_field_three
SPALLING, AGGREGATE VISBLE
custom_field_two
3
customer
1
datetime
2022-02-23T00:45:04-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
28048