Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 11, 2022, 05:27 AM
  • 18 1083_18 1082_05102022_233803.mp4

Date
05/10/2022
W/O
951809
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00675
PipeID
P14943
Time
10:27 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10094
Sewer Name
18 FLORENCE AVENUE TRUNK
City
SANTA FE SPRINGS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_951809_TV18203_MAY2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 1083
Downstream MH
18 1082
Dir. of Survey
Downstream
Length Surveyed
324.5 ft.
Total Length
324.5 ft.
Structural Index
4
Structural Quick
4J31
Structural Rating
225
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
225
Pipe schematic from manhole 18 1083 to 18 1082
MH: 18 1083MH: 18 1082downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 10830 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK3.9 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES32.9 ft. FS - Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES47.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start321.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish324.4 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK324.5 ft. AMH - Downstream Manhole, Survey Ends - 18 1082

Observation photos (3)

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    3.9 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

    32.9 ft. - Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    47.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
32.9FS
0MWM
0AMH18 1083
47.6FM
3.9CL
0MWL
0MGOCONNECTION AT THE MH 9 OC'LOCK
321.3FM
324.5AMH18 1082
324.4MGOCONNECTION AT THE MH 3 OC'LOCK

Properties (8)

additional_info
630074051022201
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2022-05-10T22:27:59-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
27555