- Date
- 05/19/2022
- W/O
- 951556
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00622
- PipeID
- P11954
- Time
- 1:34 AM
- Certificate
- U-0720-70309212
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K10118
- Sewer Name
- 15 PUENTE TRUNK
- City
- DITY OF INDUSTRY
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 15
- Page No.
- 35
- Purpose
- Routine Assessment
- Project
- RFIR_WO_951556_TV15220_MAY2022
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 10 in.
- Width
- 10 in.
- Upstream MH
- 15 0060
- Downstream MH
- 15 0059A
- Dir. of Survey
- Downstream
- Length Surveyed
- 12.5 ft.
- Total Length
- 12.5 ft.
- Structural Index
- 3
- Structural Quick
- 4132
- Structural Rating
- 10
- O&M Index
- 2
- O&M Quick
- 2200
- O&M Rating
- 4
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 14
Pipe schematic from manhole 15 0060 to 15 0059A Observation photos (4)

2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

10.8 ft. - Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

12.5 ft. - General Observation - COCKROACHES AT MH