Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 19, 2022, 10:11 AM
  • 05 0546_05 0545_05192022_042931.mp4

Date
05/19/2022
W/O
951980
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00460
PipeID
P05765
Time
3:11 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10119
Sewer Name
05 INGLEWOOD TRUNK #2
City
INGLEWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
04
Purpose
Routine Assessment
Project
WO_951980_TV05048_MAY2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
30 in.
Upstream MH
05 0546
Downstream MH
05 0545
Dir. of Survey
Downstream
Length Surveyed
348.4 ft.
Total Length
348.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
512M
O&M Rating
149
Overall Index
2
Overall Quick
Overall Rating
149
Pipe schematic from manhole 05 0546 to 05 0545
MH: 05 0546MH: 05 0545downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 05460 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES AT MH2 ft. MLC - Lining Change, Cured in place10.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start322.9 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS344.6 ft. MWM - Water Mark, 75 %of cross sectional area344.6 ft. MWL - Water Level, 40 %of cross sectional area347.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish347.3 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish348.4 ft. MGO - General Observation - COCKROACHES AT MH348.4 ft. AMH - Downstream Manhole, Survey Ends - 05 0545

Observation photos (4)

  • General Observation - COCKROACHES AT MH

    0 ft. - General Observation - COCKROACHES AT MH

  • Lining Change, Cured in place

    2 ft. - Lining Change, Cured in place

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    10.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES AT MH

    348.4 ft. - General Observation - COCKROACHES AT MH

Observations (13)

DistanceCodeObservation
344.6MWM
322.9DSZDEBRIS
2MLC
347.3DAGS
348.4MGOCOCKROACHES AT MH
0AMH05 0546
347.3DSZ
0MWL
348.4AMH05 0545
344.6MWL
0MWM
0MGOCOCKROACHES AT MH
10.7DAGS

Properties (8)

additional_info
630063051822203
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2022-05-19T03:11:00-07:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
PVCP-Folded/Reformed