Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 19, 2022, 11:01 AM
  • 05 0545_05 0544_05192022_051239.mp4

Date
05/19/2022
W/O
951980
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00460
PipeID
P05764
Time
4:01 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10119
Sewer Name
05 INGLEWOOD TRUNK #2
City
INGLEWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
04
Purpose
Routine Assessment
Project
WO_951980_TV05048_MAY2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
30 in.
Upstream MH
05 0545
Downstream MH
05 0544
Dir. of Survey
Downstream
Length Surveyed
306.9 ft.
Total Length
306.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2K00
O&M Rating
122
Overall Index
2
Overall Quick
Overall Rating
122
Pipe schematic from manhole 05 0545 to 05 0544
MH: 05 0545MH: 05 0544downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES AT MH0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - RAGGING IN MH0 ft. AMH - Upstream Manhole, Survey Begins - 05 05452 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. MLC - Lining Change, Cured in place304.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish306.9 ft. AMH - Downstream Manhole, Survey Ends - 05 0544306.9 ft. MGO - General Observation - COCKROACHES AT MH

Observation photos (5)

  • General Observation - COCKROACHES AT MH

    0 ft. - General Observation - COCKROACHES AT MH

  • General Observation - RAGGING IN MH

    0 ft. - General Observation - RAGGING IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Lining Change, Cured in place

    2 ft. - Lining Change, Cured in place

  • General Observation - COCKROACHES AT MH

    306.9 ft. - General Observation - COCKROACHES AT MH

Observations (10)

DistanceCodeObservation
306.9AMH05 0544
0MWM
2DAGS
304.9DAGS
0MGOCOCKROACHES AT MH
0MWL
2MLC
0MGORAGGING IN MH
0AMH05 0545
306.9MGOCOCKROACHES AT MH

Properties (8)

additional_info
630063051822203
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2022-05-19T04:01:30-07:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
PVCP-Folded/Reformed