Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 17, 2022, 10:20 AM
  • 15 0187_15 0186_05172022_043644.mp4

Date
05/17/2022
W/O
951607
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00605
PipeID
P12111
Time
3:20 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10111
Sewer Name
15 FERRIS ROAD TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
23
Purpose
Routine Assessment
Project
WO_951607_TV15127_MAY2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0186
Downstream MH
15 0187
Dir. of Survey
Upstream
Length Surveyed
352.1 ft.
Total Length
352.1 ft.
Structural Index
2
Structural Quick
3123
Structural Rating
9
O&M Index
2
O&M Quick
2M00
O&M Rating
140
Overall Index
2
Overall Quick
Overall Rating
149
Pipe schematic from manhole 15 0186 to 15 0187
MH: 15 0186MH: 15 0187upstream0 ft. AMH - Upstream Manhole, Survey Ends - 15 01870 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK1.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish27.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"37.1 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES45.1 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES53.3 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES78.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"84 ft. CM - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES85.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"119.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"122.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"161.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"171.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"182.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"221.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"236.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"250.9 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"283.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"298.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"309 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"332 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"350.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start352.1 ft. MGO - General Observation - COCKROACHES AT MH352.1 ft. MWM - Water Mark, 20 %of cross sectional area352.1 ft. AMH - Downstream Manhole, Survey Begins - 15 0186352.1 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (5)

  • General Observation - COCKROACHES AT MH

    0 ft. - General Observation - COCKROACHES AT MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    268.1 ft. - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    298.8 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    307 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

Observations (27)

DistanceCodeObservation
101.2TBA
352.1AMH15 0187
53.7TFA
43.1TFA
180.3TFA
350.2DAGS
0MGOCOCKROACHES AT MH
0MWM
68.6TFC
352.1MGOCONNECTION AT MH 9 O'CLOCK
268.1CM
20.1TFC
169.3TF
2DAGS
0AMH15 0186
325TFC
0MWL
190.6TFC
116TFA
315CL
307CL
130.3TFC
266.9TFA
229.9TFC
298.8CL
232.3TFC
273.9TFC

Properties (7)

additional_info
630063051622201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-05-17T03:20:08-07:00
documentation
PRO PIPE
is_lateral_inspection
false