Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 17, 2022, 09:47 AM
  • 15 0184_15 0183_05172022_035700.mp4

Date
05/17/2022
W/O
951607
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00605
PipeID
P12108
Time
2:47 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10111
Sewer Name
15 FERRIS ROAD TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
23
Purpose
Routine Assessment
Project
WO_951607_TV15127_MAY2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0184
Downstream MH
15 0183
Dir. of Survey
Downstream
Length Surveyed
232.1 ft.
Total Length
232.1 ft.
Structural Index
3
Structural Quick
3G21
Structural Rating
130
O&M Index
2
O&M Quick
2Q00
O&M Rating
180
Overall Index
2
Overall Quick
Overall Rating
310
Pipe schematic from manhole 15 0184 to 15 0183
MH: 15 0184MH: 15 0183downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 01840 ft. MGO - General Observation - COCKROACHES AT MH0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES, Start6 ft. CC - Crack Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES7 ft. CC - Crack Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES13 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES22.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"41.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"60.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"90.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"117.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"132.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"151.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"202.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"223.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES, Finish225.4 ft. AMH - Downstream Manhole, Survey Ends - 15 0183225.4 ft. MGO - General Observation - COCKROACHES AT MH232.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (3)

  • General Observation - COCKROACHES AT MH

    0 ft. - General Observation - COCKROACHES AT MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES AT MH

    225.4 ft. - General Observation - COCKROACHES AT MH

Observations (21)

DistanceCodeObservation
132.5TFC
0AMH15 0184
6CC
22.3TFC
2DAGS
41.1TFC
232.1DAGS
7CC
223.1DAGS
0MGOCOCKROACHES AT MH
0MWM
117.9TFA
151.4TFA
90.8TFC
13CL
2DAGS
202.7TFC
225.4AMH15 0183
60.1TFC
0MWL
225.4MGOCOCKROACHES AT MH

Properties (7)

additional_info
630063051622201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2022-05-17T02:47:00-07:00
documentation
PRO PIPE
is_lateral_inspection
false