Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 18, 2022, 07:35 AM
  • 08 0545_08 0544_05182022_014854.mp4

Date
05/18/2022
W/O
952079
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00021
PipeID
P00607
Time
12:35 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10114
Sewer Name
08 VICTORIA STREET TRUNK
City
RANCHO DOMINGUEZ
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Routine Assessment
Project
WO_952079_TV08029_MAY2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
12 in.
Upstream MH
08 0545
Downstream MH
08 0544
Dir. of Survey
Downstream
Length Surveyed
283.3 ft.
Total Length
283.3 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
168
O&M Index
2
O&M Quick
2J00
O&M Rating
112
Overall Index
3
Overall Quick
Overall Rating
280
Pipe schematic from manhole 08 0545 to 08 0544
MH: 08 0545MH: 08 0544downstream0 ft. MGO - General Observation - COCKROACHES AT MH0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 05452 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start6.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start139.6 ft. FS - Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES281.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish281.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish283.3 ft. MGO - General Observation - COCKROACHES AT MH283.3 ft. AMH - Downstream Manhole, Survey Ends - 08 0544

Observation photos (5)

  • General Observation - COCKROACHES AT MH

    0 ft. - General Observation - COCKROACHES AT MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES

    139.6 ft. - Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES AT MH

    283.3 ft. - General Observation - COCKROACHES AT MH

Observations (11)

DistanceCodeObservation
0MGOCOCKROACHES AT MH
139.6FS
0MWL
0MWM
281.3CM
283.3MGOCOCKROACHES AT MH
281.3DAGS
0AMH08 0545
2DAGS
283.3AMH08 0544
6.2CM

Properties (7)

additional_info
630063051722202
custom_field_three
FRACTURE/CRACKS
custom_field_two
3
customer
1
datetime
2022-05-18T00:35:30-07:00
documentation
PRO PIPE
is_lateral_inspection
false