Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 27, 2022, 04:43 AM
  • 29 0005_29 0004_05262022_231304.mp4

Date
05/26/2022
W/O
951857
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00849
PipeID
P17679
Time
9:43 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10156
Sewer Name
29 SIGNAL HILL OUTFALL TRUNK
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_951857_TV29096_MAY2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
29 0005
Downstream MH
29 0004
Dir. of Survey
Downstream
Length Surveyed
94.9 ft.
Total Length
94.9 ft.
Structural Index
4
Structural Quick
5A3C
Structural Rating
104
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
104
Pipe schematic from manhole 29 0005 to 29 0004
MH: 29 0005MH: 29 0004downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 00050 ft. MWM - Water Mark, 15 %of cross sectional area2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - MAG COAT37.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish37.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start43.7 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start94.9 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish94.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish94.9 ft. AMH - Downstream Manhole, Survey Ends - 29 0004

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    37.5 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    43.7 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0MWL
0AMH29 0005
94.9SRV
43.7SRV
94.9SAP
37.5SAV
94.9AMH29 0004
2.1SAV
37.5SAP
0MWM
2.1MGOMAG COAT

Properties (7)

additional_info
630063052622201
custom_field_three
AGGREGATE PROJECTING/REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2022-05-26T21:43:50-07:00
documentation
PROPIPE
is_lateral_inspection
false