Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 27, 2022, 08:07 AM
  • C 0309_C 0308_05272022_022428.mp4

Date
05/27/2022
W/O
951558
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00134
PipeID
P09769
Time
1:07 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10158
Sewer Name
C JOINT OUTFALL C - UNIT 6E
City
CERRITOS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_951558_TV19065_MAY2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
21 in.
Upstream MH
C 0309
Downstream MH
C 0308
Dir. of Survey
Downstream
Length Surveyed
422.5 ft.
Total Length
422.5 ft.
Structural Index
3
Structural Quick
5B3P
Structural Rating
329
O&M Index
4
O&M Quick
4332
O&M Rating
18
Overall Index
3
Overall Quick
Overall Rating
347
Pipe schematic from manhole C 0309 to C 0308
MH: C 0309MH: C 0308downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - C 03090 ft. MWM - Water Mark, 25 %of cross sectional area2.1 ft. DAGS - Deposits Attached Grease, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start10.6 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start25.4 ft. IR - Infiltration Runner, at 02 o'clock, within 8 inches of joint: YES41.7 ft. ID - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES49.8 ft. IR - Infiltration Runner, at 10 o'clock, within 8 inches of joint: YES73.1 ft. IR - Infiltration Runner, at 12 o'clock, within 8 inches of joint: YES91 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish117 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"221.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"326.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"419.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish422.5 ft. AMH - Downstream Manhole, Survey Ends - C 0308

Observation photos (7)

  • Deposits Attached Grease, 20 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES

    2.1 ft. - Deposits Attached Grease, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10.6 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Runner, at 02 o'clock, within 8 inches of joint: YES

    25.4 ft. - Infiltration Runner, at 02 o'clock, within 8 inches of joint: YES

  • Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

    41.7 ft. - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

  • Infiltration Runner, at 10 o'clock, within 8 inches of joint: YES

    49.8 ft. - Infiltration Runner, at 10 o'clock, within 8 inches of joint: YES

  • Infiltration Runner, at 12 o'clock, within 8 inches of joint: YES

    73.1 ft. - Infiltration Runner, at 12 o'clock, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
2.1DAGS
0MGOCONNECTION AT MH 3 O'CLOCK
117TF
419.2SAP
41.7ID
0MGOCONNECTION AT MH 9 O'CLOCK
0MWL
422.5AMHC 0308
10.6SRV
25.4IR
73.1IR
221.6TF
2.1SAP
0AMHC 0309
326.5TF
91SRV
0MWM
49.8IR

Properties (7)

additional_info
630063052622203
custom_field_three
AGGREGATE PROJECTING/REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2022-05-27T01:07:21-07:00
documentation
PROPIPE
is_lateral_inspection
false