Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 17, 2022, 10:01 AM
  • 15 0186_15 0185_05172022_041908.mp4

Date
05/17/2022
W/O
951996
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00605
PipeID
P12110
Time
3:01 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10112
Sewer Name
15 FERRIS ROAD TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
23
Purpose
Routine Assessment
Project
RFIR_WO_951996_TV15249_MAY2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0185
Downstream MH
15 0186
Dir. of Survey
Upstream
Length Surveyed
352.8 ft.
Total Length
352.8 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
2M00
O&M Rating
140
Overall Index
2
Overall Quick
Overall Rating
142
Pipe schematic from manhole 15 0185 to 15 0186
MH: 15 0185MH: 15 0186upstream0 ft. AMH - Upstream Manhole, Survey Ends - 15 01860 ft. MGO - General Observation - COCKROACHES AT MH2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish8.3 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES37.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"56.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"77.6 ft. RPL - Repair Localized Liner, within 8 inches of joint: YES, Finish79.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"82 ft. RPL - Repair Localized Liner, within 8 inches of joint: YES, Start114.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"121.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"152.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"178.5 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"185.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"204.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"231.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"249.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"276.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"291.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"302.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"348.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"350.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start352.8 ft. AMH - Downstream Manhole, Survey Begins - 15 0185352.8 ft. MGO - General Observation - COCKROACHES AT MH352.8 ft. MWM - Water Mark, 25 %of cross sectional area352.8 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (4)

  • General Observation - COCKROACHES AT MH

    0 ft. - General Observation - COCKROACHES AT MH

  • Repair Localized Liner, within 8 inches of joint: YES, Start

    270.8 ft. - Repair Localized Liner, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    344.5 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES AT MH

    352.8 ft. - General Observation - COCKROACHES AT MH

Observations (26)

DistanceCodeObservation
270.8RPL
2DAGS
296.2TFA
0AMH15 0185
121.5TFA
148.4TFC
352.8AMH15 0186
0MGOCOCKROACHES AT MH
174.3TFA
103TFA
0MWM
315.2TFA
167.4TFC
275.2RPL
273.7TFA
76.1TFC
352.8MGOCOCKROACHES AT MH
344.5CL
49.9TFC
0MWL
238.2TFC
231.5TFC
200.6TFA
61.1TFC
350.7DAGS
4.3TFA

Properties (7)

additional_info
630063051622202
custom_field_three
LONGITUDINAL CRACK
custom_field_two
3
customer
1
datetime
2022-05-17T03:01:29-07:00
documentation
PRO PIPE
is_lateral_inspection
false