Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 8, 2022, 11:21 AM
  • 02 1763_02 1762_03082022_043702.mp4

Date
03/08/2022
W/O
941845
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00254
PipeID
P04110
Time
3:21 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9952
Sewer Name
02 DOWNEY-BELLFLOWER EXTENSION TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
15
Purpose
Routine Assessment
Project
WO_941845_TV02102_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
15 in.
Upstream MH
02 1763
Downstream MH
02 1762
Dir. of Survey
Downstream
Length Surveyed
261.8 ft.
Total Length
261.8 ft.
Structural Index
3
Structural Quick
413I
Structural Rating
162
O&M Index
2
O&M Quick
2I1C
O&M Rating
122
Overall Index
2
Overall Quick
Overall Rating
284
Pipe schematic from manhole 02 1763 to 02 1762
MH: 02 1763MH: 02 1762downstream0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 17630 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES7.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start15 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - OPEN62 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES87.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - OPEN104.8 ft. RFJ - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR120.1 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start214.1 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Finish259 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish261 ft. MGO - General Observation - ROACHES @ MH261.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish261.8 ft. AMH - Downstream Manhole, Survey Ends - 02 1762

Observation photos (5)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO

    4 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR

    104.8 ft. - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

    120.1 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

Observations (19)

DistanceCodeObservation
261.8CM
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
104.8RFJ
7.8CM
0MWL
0AMH02 1763
261.8AMH02 1762
259DAGS
7CM
120.1RFJ
214.1RFJ
261MGOROACHES @ MH
0MWM
62FM
15TFOPEN
0MGOROACHES @ MH
2DAGS
4SSS
87.7TFOPEN

Properties (7)

additional_info
63009803722202
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-03-08T03:21:59-08:00
documentation
PRO PIPE
is_lateral_inspection
false