- Date
- 05/24/2022
- W/O
- 0952008
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00456
- PipeID
- P20594
- Time
- 1:00 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H3104
- Sewer Name
- 05 HAWTHORNE-LAWNDALE-TORRANCE TRUNK
- City
- HAWTHORNE
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 13
- Purpose
- Capital Improvement Program Assesment
- Project
- 20220523MDM_HAWTHORNE_LAWNDALE_TORRANCE_TRUNK
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 48 in.
- Upstream MH
- 05 2094
- Downstream MH
- 05 HAWTH
- Dir. of Survey
- Downstream
- Length Surveyed
- 260.8 ft.
- Total Length
- 260.8 ft.
- Structural Index
- 3
- Structural Quick
- 4221
- Structural Rating
- 10
- O&M Index
- 2
- O&M Quick
- 2100
- O&M Rating
- 2
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 12
Pipe schematic from manhole 05 2094 to 05 HAWTH Observation photos (5)

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

2 ft. - General Observation - MAG COAT 70%

40.1 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG