Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 19, 2022, 07:33 AM
  • 19 0090_19 0089_5192022_004830.mp4

Date
05/19/2022
W/O
0956462
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00722
PipeID
P15282
Time
12:33 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3100
Sewer Name
19 EAST ARTESIA TRUNK, SECTS 1,2,3,&5
City
CERRITOS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
07
Purpose
Capital Improvement Program Assesment
Project
202205MDM_EAST_ARTESIA_TRUNK_SECTS_1_2_3_5
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Upstream MH
19 0089
Downstream MH
19 0090
Dir. of Survey
Upstream
Length Surveyed
172.8 ft.
Total Length
172.8 ft.
Structural Index
5
Structural Quick
5A42
Structural Rating
60
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
64
Pipe schematic from manhole 19 0089 to 19 0090
MH: 19 0089MH: 19 0090upstream0 ft. AMH - Upstream Manhole, Survey Ends - 1:20AM0.5 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish - LONG CIRCUM REBAR CORRODED MISSING0.5 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG0.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE4.4 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - LOND CIRCUM REBAR CORRODED MISSING14 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR86.9 ft. SRC - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Finish - LONG REBAR89.1 ft. SRC - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: NO - CORRODED MISSING CIRCUM REBAR92.8 ft. SRC - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR97.9 ft. SRC - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR108.3 ft. MGO - General Observation - MAG COAT 90%114.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CORRODED MISSING CIRCUM REBAR123.7 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG135.5 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR CORRODED MISSING147.6 ft. SRC - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: NO - CORRODED MISSING CIRCUM REBAR160.4 ft. MGP - General Photograph - CORRODED CIRCUM REBAR161.5 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR CORRODED MISSING161.5 ft. SRC - Surface Reinforcement Corroded, from 03 to 01 o'clock, within 8 inches of joint: YES161.5 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG164.8 ft. MGO - General Observation - MAG COAT 10%170.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE170.8 ft. SRC - Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR170.8 ft. MGO - General Observation - MAG COAT 90%172.8 ft. AMH - Downstream Manhole, Survey Begins - 12:40AM172.8 ft. MWM - Water Mark, 60 %of cross sectional area172.8 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active172.8 ft. MWL - Water Level, 30 %of cross sectional area

Observation photos (15)

  • Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR

    2 ft. - Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR

  • General Observation - MAG COAT 90%

    2 ft. - General Observation - MAG COAT 90%

  • General Observation - MAG COAT 10%

    8 ft. - General Observation - MAG COAT 10%

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR CORRODED MISSING

    11.3 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR CORRODED MISSING

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    11.3 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Photograph - CORRODED CIRCUM REBAR

    12.4 ft. - General Photograph - CORRODED CIRCUM REBAR

  • Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: NO - CORRODED MISSING CIRCUM REBAR

    25.2 ft. - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: NO - CORRODED MISSING CIRCUM REBAR

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    49.1 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CORRODED MISSING CIRCUM REBAR

    58.6 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CORRODED MISSING CIRCUM REBAR

  • General Observation - MAG COAT 90%

    64.5 ft. - General Observation - MAG COAT 90%

  • Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    74.9 ft. - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    80 ft. - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: NO - CORRODED MISSING CIRCUM REBAR

    83.7 ft. - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: NO - CORRODED MISSING CIRCUM REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    158.8 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - LOND CIRCUM REBAR  CORRODED MISSING

    168.4 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - LOND CIRCUM REBAR CORRODED MISSING

Observations (27)

DistanceCodeObservation
11.3SRCCIRCUM REBAR CORRODED MISSING
64.5MGOMAG COAT 90%
2SSSBLISTERING PEELING CONCRETE
158.8SRCCIRCUM REBAR
0AMH12:40AM
37.3SRCCIRCUM REBAR CORRODED MISSING
0MWM
172.8AMH1:20AM
0MGOConn. @ Mh, 9 O' Clock. Active
11.3SRC
172.3SRCLONG CIRCUM REBAR CORRODED MISSING
74.9SRCCIRCUM REBAR
11.3SAMSEVERE AGG
0MWL
172.3SAMSEVERE AGG
12.4MGPCORRODED CIRCUM REBAR
85.9SRCLONG REBAR
25.2SRCCORRODED MISSING CIRCUM REBAR
172.3SSSBLISTERING PEELING CONCRETE
49.1SAMSEVERE AGG
2SRCCIRCUM REBAR
8MGOMAG COAT 10%
58.6SRCCORRODED MISSING CIRCUM REBAR
80SRCCIRCUM REBAR
83.7SRCCORRODED MISSING CIRCUM REBAR
168.4SRCLOND CIRCUM REBAR CORRODED MISSING
2MGOMAG COAT 90%

Properties (6)

custom_field_three
LONG & CIRCUM REBAR CORRODED& MISSING
custom_field_two
1
customer
LACSD
datetime
2022-05-19T00:33:42-07:00
documentation
MARTIN,REVELES,OLIVER 111,IGNACIO
is_lateral_inspection
false